Arges. The water in a city is the best in the country!

Arges. The water in a city is the best in the country!
Arges. The water in a city is the best in the country!
--

Arges. The water in a city is the best in the country!

Below we send you the results of the analyzes at the departure from the Calea Pietroasa Treatment Station and from two points of the distribution network. According to the Operational Monitoring Plan targeted by DSP Argeș.

1.Sample type: drinking water

Client: SC EDILUL CGA SA

Sampling location: Departure Calea Pietroasa Treatment Station.

Execution date: 16.04.2024.

The sample taken according to SR ISO 5667-5/2017 and ISO 19458/2007 (E).

Remarks: the water falls within the permitted values, according to Ordinance no. 7/ 18.01.2023 regarding the quality of water intended for human consumption.

pH: (allowed value: 6.5-9.5 pH units), obtained value: 7.4.

Arges. The water in a city is the best in the country!

Turbidity: (allowed value: acceptable, cf. Ordinance no. 7/2023), obtained value: 0.39 FNU.

Ammonium (NH4+): (allowed value: 0.50 mg/l), obtained value: ˂0.03 mg/l.

Nitrates (NO3-) (allowed value: 50 mg/l), obtained value: 1.21 mg/l.

Nitrites (NO2-) (allowed value: 0.50 mg/l), obtained value: ˂0.01mg/l.

Free residual chlorine (Cl2) (allowed value: 0.1-0.5 mg/l), obtained value: 0.50 mg/l.

Total hardness (allowed value: >5 German degrees), obtained value: 1.72
From a microbiological point of view, the water is compliant.

2. Sample type: drinking water

Client: SC EDILUL CGA SA

Sampling location: “CD Aricescu” Secondary School.

Execution date: 16.04.2024.

The sample taken according to SR ISO 5667-5/2017 and ISO 19458/2007 (E).

Remarks: the water falls within the allowed values, according to Ordinance no. 7/ 18.01.2023.

pH: (allowed value: 6.5-9.5 pH units), obtained value: 7.5.

Turbidity: (allowed value: acceptable, cf. Ordinance no. 7/2023), obtained value: 0.81 FNU.

Ammonium (NH4+): (allowed value: 0.50 mg/l), obtained value: ˂0.03 mg/l.

Nitrates (NO3-) (allowed value: 50 mg/l), obtained value: 0.98 mg/l.

Nitrites (NO2-) (allowed value: 0.50 mg/l), obtained value: ˂0.01 mg/l.

Free residual chlorine (Cl2) (allowed value: 0.1-0.5 mg/l), obtained value: 0.10 mg/l.

Total hardness (allowed value: >5 German degrees), obtained value: 1.71
From a microbiological point of view, the water is compliant.

3. Sample type: drinking water

Client: SC EDILUL CGA SA

Sampling place: Valea Bărbusii.

Execution date: 16.04.2024.

The sample taken according to SR ISO 5667-5/2017 and ISO 19458/2007 (E).

Remarks: the water falls within the allowed values, according to Ordinance no. 7/ 18.01.2023.

pH: (allowed value: 6.5-9.5 pH units), obtained value: 7.3.

Turbidity: (allowed value: acceptable, cf. Ordinance no. 7/2023), obtained value: 0.62 FNU.

Ammonium (NH4+): (allowed value: 0.50 mg/l), obtained value: ˂0.03 mg/l.

Nitrates (NO3-) (allowed value: 50 mg/l), obtained value: 1.23 mg/l.

Nitrites (NO2-) (allowed value: 0.50 mg/l), obtained value: ˂0.01 mg/l.

Free residual chlorine (Cl2) (allowed value: 0.1-0.5 mg/l), obtained value: 0.18 mg/l.

Total hardness (allowed value: >5 German degrees), obtained value: 1.69
From a microbiological point of view, the water is compliant.

Elaborated, Head of Laboratory Service, Eng. Laura Pepenel
General Director, Eng. Mihail Vasilescu

Follow the news of Ziarului din Muscel also on the Facebook page, on the Readers of Ziarului din Muscel group, on Tik Tok or directly on the WhatsApp channel.


The article is in Romanian

Tags: Arges water city country

-

PREV The regulation for this year’s participatory budgeting campaign was approved
NEXT More than 200 firefighters ready to intervene during the May 1 and Easter mini-holiday.