Below we send you the results of the analyzes at the departure from the Calea Pietroasa Treatment Station and from two points of the distribution network (according to the Operational Monitoring Plan targeted by DSP Argeș):
1.Sample type: drinking water
Client: SC EDILUL CGA SA
Sampling location: Departure Calea Pietroasa Treatment Station
Execution date: 23.04.2024
The sample taken according to SR ISO 5667-5/2017 and ISO 19458/2007 (E)
Remarks: the water falls within the allowed values, according to Ordinance no. 7/ 18.01.2023 on the quality of water intended for human consumption, approved by Law no. 96/2024
pH: (allowed value: 6.5-9.5 pH units), obtained value: 7.4
Turbidity: (allowed value: acceptable, cf. Ordinance no. 7/2023), obtained value: 0.36 FNU
Ammonium (NH4+): (allowed value: 0.50 mg/l), obtained value: ˂0.03 mg/l
Nitrates (NO3–) (allowed value: 50 mg/l), obtained value: 1.18 mg/l
Nitrites (NO2–) (allowed value: 0.50 mg/l), obtained value: ˂0.01mg/l
Residual chlorine (Cl2) free (allowed value: 0.1-0.5 mg/l), obtained value: 0.50 mg/l
Total hardness (allowed value: >5 German degrees), obtained value: 1.73
From a microbiological point of view, the water is compliant.
2. Sample type: drinking water
Client: SC EDILUL CGA SA
Sampling location: Schitu Golești High School
Execution date: 23.04.2024
The sample taken according to SR ISO 5667-5/2017 and ISO 19458/2007 (E)
Remarks: the water falls within the permitted values, according to Ordinance no. 7/ 18.01.2023, approved by Law no. 96/2024
pH: (allowed value: 6.5-9.5 pH units), obtained value: 7.4
Turbidity: (allowed value: acceptable, cf. Ordinance no. 7/2023), obtained value: 1.10 FNU
Ammonium (NH4+): (allowed value: 0.50 mg/l), obtained value: ˂0.03 mg/l
Nitrates (NO3–) (allowed value: 50 mg/l), obtained value: 1.27 mg/l
Nitrites (NO2–) (allowed value: 0.50 mg/l), obtained value: ˂0.01 mg/l
Residual chlorine (Cl2) free (allowed value: 0.1-0.5 mg/l), obtained value: 0.18 mg/l
Total hardness (allowed value: >5 German degrees), obtained value: 1.74
From a microbiological point of view, the water is compliant.
3. Sample type: drinking water
Client: SC EDILUL CGA SA
Sampling location: Mărcuș neighborhood
Execution date: 23.04.2024
The sample taken according to SR ISO 5667-5/2017 and ISO 19458/2007 (E)
Remarks: the water falls within the permitted values, according to Ordinance no. 7/ 18.01.2023, approved by Law no. 96/2024
pH: (allowed value: 6.5-9.5 pH units), obtained value: 7.5
Turbidity: (allowed value: acceptable, cf. Ordinance no. 7/2023), obtained value: 0.62 FNU
Ammonium (NH4+): (allowed value: 0.50 mg/l), obtained value: ˂0.03 mg/l
Nitrates (NO3–) (allowed value: 50 mg/l), obtained value: 1.25 mg/l
Nitrites (NO2–) (allowed value: 0.50 mg/l), obtained value: ˂0.01 mg/l
Residual chlorine (Cl2) free (allowed value: 0.1-0.5 mg/l), obtained value: 0.10 mg/l
Total hardness (allowed value: >5 German degrees), obtained value: 1.68
From a microbiological point of view, the water is compliant.
Elaborated, Head of Laboratory Service, Eng. Laura Pepenel
General Director, Eng. Mihail Vasilescu