SC EDILUL CGA SA – WATER QUALITY

--

Below we send you the results of the analyzes at the departure from the Calea Pietroasa Treatment Station and from two points of the distribution network (according to the Operational Monitoring Plan targeted by DSP Argeș):

1.Sample type: drinking water

Client: SC EDILUL CGA SA

Sampling location: Departure Calea Pietroasa Treatment Station

Execution date: 23.04.2024

The sample taken according to SR ISO 5667-5/2017 and ISO 19458/2007 (E)

Remarks: the water falls within the allowed values, according to Ordinance no. 7/ 18.01.2023 on the quality of water intended for human consumption, approved by Law no. 96/2024

pH: (allowed value: 6.5-9.5 pH units), obtained value: 7.4

Turbidity: (allowed value: acceptable, cf. Ordinance no. 7/2023), obtained value: 0.36 FNU

Ammonium (NH4+): (allowed value: 0.50 mg/l), obtained value: ˂0.03 mg/l

Nitrates (NO3) (allowed value: 50 mg/l), obtained value: 1.18 mg/l

Nitrites (NO2) (allowed value: 0.50 mg/l), obtained value: ˂0.01mg/l

Residual chlorine (Cl2) free (allowed value: 0.1-0.5 mg/l), obtained value: 0.50 mg/l

Total hardness (allowed value: >5 German degrees), obtained value: 1.73

From a microbiological point of view, the water is compliant.

2. Sample type: drinking water

Client: SC EDILUL CGA SA

Sampling location: Schitu Golești High School

Execution date: 23.04.2024

The sample taken according to SR ISO 5667-5/2017 and ISO 19458/2007 (E)

Remarks: the water falls within the permitted values, according to Ordinance no. 7/ 18.01.2023, approved by Law no. 96/2024

pH: (allowed value: 6.5-9.5 pH units), obtained value: 7.4

Turbidity: (allowed value: acceptable, cf. Ordinance no. 7/2023), obtained value: 1.10 FNU

Ammonium (NH4+): (allowed value: 0.50 mg/l), obtained value: ˂0.03 mg/l

Nitrates (NO3) (allowed value: 50 mg/l), obtained value: 1.27 mg/l

Nitrites (NO2) (allowed value: 0.50 mg/l), obtained value: ˂0.01 mg/l

Residual chlorine (Cl2) free (allowed value: 0.1-0.5 mg/l), obtained value: 0.18 mg/l

Total hardness (allowed value: >5 German degrees), obtained value: 1.74

From a microbiological point of view, the water is compliant.

3. Sample type: drinking water

Client: SC EDILUL CGA SA

Sampling location: Mărcuș neighborhood

Execution date: 23.04.2024

The sample taken according to SR ISO 5667-5/2017 and ISO 19458/2007 (E)

Remarks: the water falls within the permitted values, according to Ordinance no. 7/ 18.01.2023, approved by Law no. 96/2024

pH: (allowed value: 6.5-9.5 pH units), obtained value: 7.5

Turbidity: (allowed value: acceptable, cf. Ordinance no. 7/2023), obtained value: 0.62 FNU

Ammonium (NH4+): (allowed value: 0.50 mg/l), obtained value: ˂0.03 mg/l

Nitrates (NO3) (allowed value: 50 mg/l), obtained value: 1.25 mg/l

Nitrites (NO2) (allowed value: 0.50 mg/l), obtained value: ˂0.01 mg/l

Residual chlorine (Cl2) free (allowed value: 0.1-0.5 mg/l), obtained value: 0.10 mg/l

Total hardness (allowed value: >5 German degrees), obtained value: 1.68

From a microbiological point of view, the water is compliant.

Elaborated, Head of Laboratory Service, Eng. Laura Pepenel

General Director, Eng. Mihail Vasilescu